Water supply network monitoring system, residual chlorine, turbidity pH meter -[KNF-400B] is based on the "drinking water sanitation standards" related requirements, strengthen drinking water safety management to provide basis and support and research and development of water quality online monitoring system, mainly for the turbidity of water quality, residual chlorine, PH, temperature to implement online and early warning, the product adopts modular design, Easy to install and maintain, suitable for single point and large area distribution monitoring requirements.
Water supply pipe network monitoring system, residual chlorine, turbidity pH meter -[KNF-400B]
Water supply network monitoring system KNF-400B is an online water quality monitoring system developed based on the relevant requirements of Drinking Water Sanitation Standards to provide basis and support for strengthening drinking water safety management. It mainly implements online and early warning for turbidity, residual chlorine, PH and temperature of water quality. The product adopts modular design and is easy to install and maintain. Suitable for single point and large area distribution monitoring requirements.
At the same time, water supply network monitoring system, residual chlorine, turbidity pH meter -[KNF-400B] based on the water quality online terminal monitoring equipment, data acquisition and transmission, environmental monitoring management system and other aspects of the research and development, production, operation experience, for drinking water monitoring characteristics, Shenzhen Kainafo has a long-term, stable, effective solution. The system can realize the digital management of the whole process of drinking water monitoring and analysis, data collection and transmission, equipment counter-control, monitoring and early warning, promote the information and modernization of drinking water management, can be complete, improve the management level.
Technical indicators of KNF-400B water quality monitoring system for water supply network:
index parameter | pH | turbidity | Residual chlorine
| temperature | Dissolved oxygen (optional) | Conductivity (optional)
| ORP (optional)
|
Measuring principle | Glass electrode method | 90 Scattered light type | Current method | internally installed | Fluorescence spectrophotometry | Conductivity method | Platinum electrode |
measuring range | 0-14pH | 0-10NTU | 0-2mg/L | 0-50℃ | 0-20mg/L | 0-5000µS | 0-±1999mV |
resolution ratio | 0.01pH | 0.01NTU | 0.005mg/L | 0.1℃ | 0.01mg/L | 0.01µS | 1mV |
precision | ±0.05pH | ≤±0.1NTU | ≤0.5mg/L | ±0.5℃ | ≤0.2mg/L | 1% | 1mV |
power consumption | About 0.3W | About 1W | About 0.5W | Inside the electrode | 0.5W | 0.5W | About 0.5W |
display system | 7-inch touch LCD, which can display data and graphs, historical data and curves, and alarm records in real time. | ||||||
Data storage | Built-in data storage, u disk countdown data table | ||||||
Data reporting | The configurable reporting interval can be uploaded to the cloud through GPRS. | ||||||
data output | RS485(modbus-rtu protocol), 4G wireless output, NB, etc. | ||||||
operating voltage | AC100-240V@DC12-24V | ||||||
outline dimension | 860X500X250mm | ||||||
Maintenance cycle | Simple cleaning can be done in about 3-6 months, and the residual chlorine needs to be replaced and electrolyte added in about 3-6 months according to the water quality. | ||||||
Cloud platform monitoring | It has cloud platform monitoring function, alarm, monitoring, WeChat binding and other functions. | ||||||
Software and certification | Have software registration certificate, ISO9001, ISO14001, measurement test report. | ||||||
Automatic blowdown | Built-in automatic blowdown device |